6 Testing & Troubleshooting
6-3
Alternate Comm Receiver
Trouble
This condition is generated when the GPRS/
Ethernet module loses supervision or fails to
initialize a receiver.
Refer to the TL260/TL260GS/TL265/TL265GS/GS2060/GS2065
Installation Manual for more details.
Alternate Comm Fault This condition is created when the PC9155
loses communication with an Ethernet or
GPRS module.
Refer to the TL260/TL260GS/TL265/TL265GS/GS2060/GS2065
Installation Manual for more details.
Alternate Comm Config
SMS Trouble
This condition is created when the GPRS/
Ethernet module detects an SMS Connect 24
Configuration failure trouble.
Refer to the TL260/TL260GS/TL265/TL265GS/GS2060/GS2065
Installation Manual for more details.
Trouble [1] Service Required Press [1] to determine specific trouble
Low Battery
Main panel battery less than 11.4V +/- 0.1V.
NOTE: This trouble condition will not clear
until the battery voltage is 12.5V
+/- 0.1V.
NOTE: If battery is new allow 24 hrs. to charge.
Verify voltage measured across AC terminals is 16-18 VAC.
Verify voltage measured across battery terminals is 12.5V +/- 0.1V.
Replace transformer if required.
Disconnect then reconnect battery leads.
General System Trouble
The system has detected the presence of a RF
Jam for 20 seconds or communications with
the wireless receiver have failed causing a
hardware fault.
Check Event Buffer to determine specific trouble.
If buffer logs RF Jam trouble, check for external 433MHZ signal
sources. To disable RF Jam, enable option [7] in program section
[804] subsection [900].
If buffer logs “Hardware Fault” - replace panel.
General System Tamper
Cover tamper tripped.
Verify tamper buttons are installed into backplate and frontplate,
and that the frontplate is fully in place.
Verify panel is properly secured to wall with the front cover on.
Trouble [2] AC Failure
AC Failure No AC at panel AC input terminals.
Verify voltage measured across AC terminals is 16-18VAC.
Replace transformer if required.
Trouble [3] Telephone Line Trouble
Telephone Line Trouble Phone line voltage at TIP, RING on main
panel less than 3V
DC.
Measure voltage across TIP and RING on the panel:
No phone off-hook – 50VDC (approx.).
Any phone off-hook – 5VDC (approx.).
Wire incoming line directly to TIP and RING.
If trouble clears, check wiring or the RJ-31x phone jack.
Trouble [4] Failure to Communicate
Failure to Communicate
Panel fails to communicate one or more
events to central station.
Connect a handset to TIP and RING of the control panel. Monitor
for the following conditions:
Continuous dial tone
Reverse TIP and RING.
Recorded operator message comes on
Verify correct phone number is programmed.
Dial the number programmed using a regular telephone to deter-
mine if a [9] must be dialed or if 800 service is blocked.
Panel does not respond to handshakes
Verify the format programmed is supported by the central station.
Panel transmits data multiple times without receiving a hand-
shake
Verify account number and reporting codes are correctly pro-
grammed.
Contact ID and Pulse formats
Program a HEX [A] to transmit a digit [0].
SIA format
Program a digit [0] to transmit a digit [0].
GSM/Ethernet
Refer to the TL260GS/TL265GS/GS2060/GS2065 Installation
Manual for troubleshooting actions.